Logic solver channel data is sent to controllers for use in non-SIS modules. By default the data is sent once per second. If you need the data at a faster update rate you can select the Enable fast I/O updates to the DeltaV Controller check box on the logic solver properties dialog. This sets the update rate to once per 100 ms, but increases the load on the local bus.
This checkbox affects only non-HART data.