| SLS 1508 SIS property | Limits |
|---|---|
|
SLS 1508 Logic Solvers on a single DeltaV controller (can be mixed between simplex and redundant) |
32 |
|
Secure parameters per SLS 1508 Logic Solver |
8 (16 if high-density) |
|
Secure parameter per SIS module (depends on if the logic solver the module is assigned to is configured for high-density secure parameters) |
8 (16 if high-density) |
|
Logic solvers that can be System Global Publishers |
16 |
|
System Global Secure Parameters in an SLS 1508 system: 16 Logic Solvers × 8 System parameters (16 × 16 for high density). |
128 (256 if high-density) |
|
Logic Solver I/O channels on a single DeltaV controller: 16 I/O channels × 32 Logic Solvers. |
512 |
|
SISNet Repeaters connected in a ring (The primary and secondary SISNet Repeater rings are separate and independent rings. ) |
100 |
|
SLS 1508 Logic Solvers in a single DeltaV system: 100 controllers × 32 Logic Solvers per controller. |
3200 |
|
Function blocks per SIS module |
250(1) |
|
User-defined parameters per SIS module |
247 |
|
SIS Modules in a Logic Solver |
4 |
|
Non-secure parameter references in a logic solver |
24 |
|
Domains in an SIS Network |
15 |
|
Simulated logic solvers running in the ProfessionalPLUS workstation |
32 |
|
Simulated logic solvers running in an Application Station |
32 |
| SIS capacity | Per controller | Per domain | Per system |
|---|---|---|---|
|
Domain and system global publishers |
|||
|
Maximum number of logic solvers that can be domain global publishers |
16 |
32 |
480 (15 domains × 32 domain publishers.) |
|
TOTAL number of logic solvers that can publish data globally |
32 (16 Domain publishers + 16 system publishers.) |
48 (32 Domain publishers + 16 system publishers.) |
496 (480 Domain publishers + 16 system publishers.) |
|
Domain and system secure parameters |
|||
|
Maximum number of domain secure parameters |
128 (256 if high-density) ( 16 Logic Solvers × 8 domain parameters (16 × 16 for high density.)) |
256 (512 if high-density) (32 domain publishers × 8 domain parameters (32 × 16 for high density.)) |
3840 (7680 if high-density) (480 domain publishers × 8 domain parameters (480 × 16 for high density.)) |
|
TOTAL number of secure parameters published globally |
256 (512 if high-density) (128 domain parameters + 128 system parameters (256 + 256 for high density.)) |
384 (768 if high-density) (256 domain parameters + 128 system parameters (512 + 256 for high density.)) |
3968 (7936 if high-density) (3840 domain parameters + 128 system parameters (7680 + 256 for high density.)) |
| Common SIS capacities | Limits |
|---|---|
|
Temporary variables defined using VAR…END_VAR per expression |
32 |
|
Function blocks in the top level of an SIS module |
127(1) |
|
Function blocks per composite |
127(1) |