SLS 1508 SIS diagnostics > Logic solver diagnostic parameters

Card Status logic solver diagnostic parameter

Table: Card Status diagnostic parameter

Parameter name in Diagnostics Explorer

Context in Diagnostics Explorer

Runtime path

Description

Status

Card

CTL_NAME/IO1/Cxx/STATUS

Status of the logic solver card

Table: Card Status condition text

Condition Text in STATUS

Meaning

No Card

Card is not communicating with controller

Not Operational

Card is in reduced operational mode because a failure was detected during or immediately after powerup tests.

Subsystem Fault

One or more subsystems have a condition present that causes Bad OINTEG.

Cfg Mismatch with Controller

Controller sees mismatch between configured and reported DEV_CRC.

Unconfigured Unit

Controller has configuration for slot, but card has no configuration.

Termination Block Incorrectly Installed

Card is in even slot.

Good, No Installed Config

Controller has no configuration for the card slot.