Parameter name in Diagnostics Explorer |
Context in Diagnostics Explorer |
Runtime path |
Description |
|---|---|---|---|
|
ControlStatus |
Card |
CTL_NAME/IO1/Cxx/CONTROL_STATUS |
Status of the control subsystem in the main processors of the logic solver card |
|
Condition Text in ControlStatus |
Meaning |
Mapping to Alert Condition |
Impacts Integrity? |
|---|---|---|---|
|
Non-critical Mismatch Between Main Processor Data |
The main processors have determined a mismatch in dynamic data other than outputs and secure parameter values. |
ADVISE_ALERTS Non-critical Mismatch Between Main Processor Data |
Y |
|
Modules Not Executing at Configured Scan Rate |
The logic solver has set the actual scan rate longer than the configured scan rate based on the estimate of execution time at download. |
MAINT_ALERTS Modules Not Executing at Configured Scan Rate |
Y |
|
Error on Non-Volatile Memory Restore |
Main Processor 1 was not able to restore saved parameter records after a powerup or restart and has initialized non-volatile memory. The card is in an unconfigured state. The error is cleared on the next download or reset. |
MAINT_ALERTS Non-Volatile Memory Battery or Chip Failure |
Y |
|
Less Than 5 Percent Parameter Records Available |
Non-volatile memory availability to store parameter change records is low. |
ADVISE_ALERTS Non-volatile Memory Alert |
Y |
|
Cyclic Redundancy Check Error on Non-Volatile Memory |
A CRC error occurred when writing a parameter record or during periodic check |
MAINT_ALERTS Non-Volatile Memory Battery or Chip Failure |
Y |
|
Control Event Lost |
A control event was not communicated to the controller because the buffer was full. |
None |
N |
|
All Non-Volatile Memory Parameter Records Exhausted |
No more non-volatile memory is available for parameter change records |
ADVISE_ALERTS Non-volatile Memory Alert |
Y |
|
Proof Test Reminder is Active |
The logic solver proof test timer is within the reminder period of the required interval. |
ADVISE_ALERTS Proof Test Reminder is Active |
N |
|
Proof Test is Overdue |
The logic solver proof test timer has exceeded the required interval. |
ADVISE_ALERTS Proof Test is Overdue |