Parameter name in Diagnostics Explorer |
Context in Diagnostics Explorer |
Runtime path |
Description |
|---|---|---|---|
|
IODevStatus |
Card |
CTL_NAME/IO1/Cxx/IO_DEV_STATUS |
Status of the I/O device subsystem in the I/O Processor of the logic solver card |
|
Condition Text in IODevStatus |
Meaning |
Mapping to Alert Condition |
Impacts Integrity? |
|---|---|---|---|
|
Self-Test Incomplete |
A periodic I/O processor memory test did not complete in the allotted time. The condition clears when the test complete. |
ADVISE_ALERTS Self-Test Incomplete |
Y |
|
Calibration Range Error |
One or more calibration values outside of valid range. |
MAINT_ALERTS Calibration Data Questionable |
Y |
|
Default Calibration Detected |
No manufacturing calibration data is present. |
MAINT_ALERTS Calibration Data Questionable |
Y |