SLS 1508 SIS diagnostics > Logic solver diagnostic parameters

IODevStatus logic solver diagnostic parameter

Table: IODevStatus diagnostic parameter

Parameter name in Diagnostics Explorer

Context in Diagnostics Explorer

Runtime path

Description

IODevStatus

Card

CTL_NAME/IO1/Cxx/IO_DEV_STATUS

Status of the I/O device subsystem in the I/O Processor of the logic solver card

Table: IODevStatus condition text

Condition Text in IODevStatus

Meaning

Mapping to Alert Condition

 Impacts Integrity?

Self-Test Incomplete

A periodic I/O processor memory test did not complete in the allotted time. The condition clears when the test complete.

ADVISE_ALERTS Self-Test Incomplete

Y

Calibration Range Error 

One or more calibration values outside of valid range.

MAINT_ALERTS Calibration Data Questionable

Y

Default Calibration Detected

No manufacturing calibration data is present.

MAINT_ALERTS Calibration Data Questionable

Y