SLS 1508 SIS diagnostics > Logic solver diagnostic parameters

P2PStatus logic solver diagnostic parameter

Table: P2PStatus diagnostic parameter

Parameter name in Diagnostics Explorer

Context in Diagnostics Explorer

Runtime path

Description

P2Pstatus

Card

CTL_NAME/IO1/Cxx/P2P_STATUS

Status of the peer-to-peer subsystem (SISNet interface) in the main processors of the logic solver card

Table: P2PStatus condition text

Condition Text in P2PStatus

Meaning

Mapping to Alert Condition

Impacts Integrity?

Main Processor 1 Primary Receive Error

Number of consecutive scans with primary peer bus receive errors was exceeded on MP1.  May be due to a transmit problem on another card.

MAINT_ALERTS

SISNet Error

Y

Main Processor 1 Secondary Receive Error

Number of consecutive scans with secondary peer bus receive errors was exceeded on MP1.  May be due to a transmit problem on another card.

MAINT_ALERTS

SISNet Error

Y

Main Processor 1 Synchronization Adjustment

MP1 has exceeded the allowed adjustment for the peer bus slot timer.

MAINT_ALERTS

SISNet Error

Y

Main Processor 1 High Error Rate

MP1 sees a high percentage error rate in peer bus communications.

ADVISE_ALERTS

SISNet High Error Rate

Y

Main Processor 2 Primary Receive Error

Number of consecutive scans with primary peer bus receive errors was exceeded on MP2.  May be due to a transmit problem on another card.

MAINT_ALERTS

SISNet Error

Y

Main Processor 2 Secondary Receive Error

Number of consecutive scans with secondary peer bus receive errors was exceeded on MP2.  May be due to a transmit problem on another card.

MAINT_ALERTS

SISNet Error

Y

Main Processor 2 Synchronization Adjustment

MP2 has exceeded the allowed adjustment for the peer bus slot timer.

MAINT_ALERTS

SISNet Error

Y

Main Processor 2 High Error Rate 

MP2 sees a high percentage error rate in peer bus communications.

ADVISE_ALERTS

SISNet High Error Rate

Y

Main Processor 2 Primary Transmit Error 

Number of consecutive scans with primary peer bus transmit errors was exceeded. Usually indicates that this card should be replaced.

MAINT_ALERTS

SISNet Error

Y

Main Processor 2 Secondary Transmit Error 

Number of consecutive scans with secondary peer bus transmit errors was exceeded. Usually indicates that this card should be replaced.

MAINT_ALERTS

SISNet Error

Y

Duplicate Global Publisher Detected

Two logic solvers are assigned to the same global slot.

MAINT_ALERTS

SISNet Error

Y