Parameter name in Diagnostics Explorer |
Context in Diagnostics Explorer |
Runtime path |
Description |
|---|---|---|---|
|
PastError |
Card |
CTL_NAME/IO1/Cxx/PAST_ERROR |
The fatal error that caused the most recent reset of the logic solver card |
|
Condition Text in PastError |
Meaning |
Action |
Mapping to Alert Condition |
|---|---|---|---|
|
Program Assertion |
Unspecified internal software error, e.g. corruption of program causes a null pointer to be returned. |
If the fatal condition is persistent, do a manual reset of affected card and contact technical support. If the fatal condition was momentary, contact technical support to report the error. |
Bits map directly to identical bits in FAILED_ALERTS in a simplex logic solver. |
|
Resource Error |
System software could not obtain a hardware or software resource. |
||
|
Memory Test Failure |
Failure detected in periodic main processor RAM test or powerup test of RAM and NVM. |
||
|
Uncommanded Switchover |
Active logic solver has gone through reset (becoming Standby) because it was not communicating with controller. |
||
|
Control Subsystem Compare Error |
The main processors detected a mismatch in outputs or secure parameter data. |
||
|
Timeout on Inter-Processor Link Between Main Processor 1 and Main Processor 2 |
Number of scans exceeded for a main processor to respond to the other. |
||
|
Timeout Between Main Processor 2 and I/O Processor |
Number of scans exceeded for IOP to respond to MP2. Fatal errors detected by IOP are revealed by this condition. |
||
|
Main Processor 2 Compare of I/O Processor Data Failed |
MP2 validates the calculations being done by IOP. A mismatch in the results of the calculations causes this condition. |
||
|
Main Processor 2 Compare of I/O Processor Frequency Failed |
MP2 has detected that IOP is communicating at an improper rate. |
||
|
Task Checkpoint Error |
A control or communications task did not have a timely or proper completion. |
||
|
Hardware Watchdog Failure |
A powerup test failed on a watchdog timer or a processor did not arm its watchdog within the window during operation. |
||
|
Unspecified Hardware Error |
Unspecified hardware error such as failure of the commission circuitry. |
||
|
Control Subsystem Scheduling Error |
MP2 is unable to complete writing of output values prior to beginning new control execution. |
Change to a slower logic solver scan rate and re-download. |
|
|
Dual Active Logic Solvers |
One logic solver of a pair has gone through reset because both logic solvers were in the active role. |
Probably due to an issue with the redundancy link. Problem could be with either logic solver (not necessarily the one that reset). Start by replacing the standby unit, then perform a switchover to it. If the condition returns, replace the other logic solver. |
NA |