Parameter name in Diagnostics Explorer |
Context in Diagnostics Explorer |
Runtime path |
Description |
|---|---|---|---|
|
RedunStatus |
Card |
CTL_NAME/IO1/Cxx/REDUN_STATUS |
Status of the redundancy subsystem in Main Processor 1 of the logic solver card |
|
Condition Text in RedunStatus |
Meaning |
Mapping to Alert Condition |
Impacts Integrity? |
|---|---|---|---|
|
Revision Mismatch |
The firmware revision of the Standby card is incompatible with the Active card's revision. |
None |
Y |
|
Dual Active Logic Solvers |
This card and partner card both see role as Active card. |
None – PAST_ERROR condition |
Y |
|
High Redundancy Link Error Rate |
MP1 sees a high percentage communications error rate on the redundancy link. |
ADVISE_ALERTS High Redundancy Link Error Rate |
Y |
|
Partner Not Present |
Partner card is not responding to heartbeat messages. |
MAINT_ALERTS Partner Not Present |
Y |
|
Partner Not Available |
Partner card is not responding to heartbeat messages or is responding but is not configured. |
MAINT_ALERTS Partner Not Available |
Y |