SIS function blocks > SIS Advanced Function Blocks > Logic Solver Discrete Voter function block

Logic Solver Discrete Voter function alarm detection

Due to the number of conditions in each block and the potential for having many voter blocks in a module, some of the DVTR_ALERTS conditions propagate to the module level parameter SIF_ALERTS. The following table lists the block alarm conditions that propagate to the module level. Active conditions in any Discrete Voter block set the corresponding alerts in the module level SIF_ALERTS parameter.

Alarm Condition in DVTR_ALERTS

Alert in Module Parameter SIF_ALERTS

Trip Active

Trip consensus in an AVTR or DVTR block

Bypass Active

An AVTR or DVTR block has a bypassed input

Startup Override Active

An AVTR or DVTR block has an active startup override

Expiration Reminder

A bypass or startup override is about to expire in an AVTR or DVTR block

Inhibited

A function block is inhibited

Alarm conditions do not propagate when the REPORT_OPTS option Alarm conditions do not roll up to module level is selected. You might want to prevent propagation when the voting scheme is used to calculate a permissive rather than an interlock or trip condition.