SIS function blocks > SIS Timer/Counter Blocks > Logic Solver On Delay Timer function block

Logic Solver On Delay Timer function block parameters

The following table lists the system parameters for the LSOND function block:

Table: LSOND Function Block System Parameters

Parameter

(Data Type)

Default Values (Units)

Characteristics

Description

ELAPSED_TIMER

(Floating point)

0

(Seconds)

Access:

Tuning

NVM:

Preserved on Download

The elapsed time since the True discrete input value was active.

IN_D

(Discrete with status)

0

Access:

Tuning

NVM:

Restored on Restart

The discrete input value and status used to trigger the timed discrete output value.

OUT_D

(Discrete with status)

0

NVM:

Preserved on Download

The discrete output value and status.

TIME_DURATION

(Floating point)

2

(Seconds)

Access:

Configurable, Tuning

NVM:

Restored on Restart

Specifies the time delay after IN_D is set to 1 before OUT_D becomes 1. Enter a value between 0 and 1.0737e+008.