Import the SLS 1508 configuration from the real
system
On the simulation system:
Set up the ProfessionalPLUS workstation and assign licenses for
multi-node simulation.
Create Application Stations as needed to simulate the controllers
in the configuration.
Set the controller alias names in Simulated Logic Solvers
subsystem on the ProfesionalPLUS workstation and Application
Stations to match the real system controller names.
Create logic solver cards in the correct slots in the Logic
Solvers subsystem.
Import the SIS Network subsystem you exported from the real system
(default export file name is SIS Network.fhx).
Areas and SIS modules are created as required and the modules are
assigned to logic solvers.
Commission the logic solvers.
Download the logic solvers.
The DownloadProgress.log file includes the message that the logic
solver download was different from the last download.