DeltaV SIS security > Protected SIS composite templates > Protected SIS composite template behavior

SIS Composite template run-time behavior

Online parameter changes to internal parameters of Embedded Composites created from protected SIS Composite Templates are not allowed, either by secure writes or Calculation/Logic block writes. A Calculation/Logic block within a protected composite can write to parameters within that protected composite.

Writes are not allowed to protected parameters or parameters of a block within a protected composite. If a user attempts to write a value an error message appears. If a Calc block attempts the write, the Output Failure bit in the Calc blocks BLOCK_ERR parameter is set.

If users need to change parameter values of a block within a protected SIS Composite Template from the operator environment, promote the parameters to composite-level parameters. Make sure the input parameters are included in SIS Parameter Security and assigned an appropriate lock or change the default lock for SIS parameters.
Note

Use the SIS Data Entry Expert to create DeltaV Operate objects so users can change composite block values.