Configure a physical SLS 1508 logic solver card

Create Logic Solver cards under controller I/O subsystems in the Physical Network. The cards can also be auto-sensed. Logic Solver card icons are different from other card icons. You assign a Logic Solver in the SIS Network to the physical Logic Solver card.

  1. Navigate to the I/O subsystem under a controller.
  2. Right-click and select New Card.
  3. Select SIS Cards as the card class.

    Logic Solver is the only choice in the SIS card class.

  4. Select the slot position, which should always be an odd number for Logic Solver cards.
    Note

    The Logic Solver card occupies two slots for a simplex and four slots for a redundant Logic Solver.

  5. If the card is redundant, select the Card is redundant check box.
  6. Click OK.