Item
Specification
Number of channels
16
Isolation
Each channel is optically isolated from the system and factory tested to 1500 VDC. No channel-to-channel isolation.
Nominal signal range (span)
On state - 20 mA
Off state - 0 or 4 mA (configurable)
Full signal range
0 to 24 mA
Safety/diagnostic accuracy
5% of span
Resolution
12 bits
Compliance voltage
20 mA into 600 Ω load
Open-loop detection
< 1.0 mA - when the output drifts 15% out of the configured value