When you use the DeltaV Device Commissioner application to sense devices under a CSLS, the application performs the following steps:
If an Analog Input CHARM is already configured and is not configured for HART Analog Input, the application does not sense devices connected to that CHARM.
For configured two-state DVC CHARMs, connected devices will be sensed either if current is present in the wire or if the OFF_CURRENT parameter of the CHARM is set to 4 mA. If the OFF_CURRENT parameter is set to 0 mA and there is no current present in the wire, a connected device will not be sensed and the application will add an item to the punchlist for the CHARM.