Interface Specifications > Mass Termination Blocks

Redundant Discrete Input 40-Pin Mass Termination Block

Installation notes

Note

The termination fault detection feature is available only when the redundant DI, 32-Channel, 24 VDC, Dry Contact Series 2 Plus card is used with the Redundant Discrete Input 40-Pin Mass Termination Block connected to the DI Mass Connection Solution.

Specifications

Table: Redundant Discrete Input 40-Pin Mass Termination Block specifications

Item

Specification

Voltage rating

30 VDC

Maximum current

5 mA per channel; 160 mA total

Mounting

Assigned slots of I/O carrier. The lower slot number must be odd and the upper slot number must be the next higher even number. For example, slots 1 and 2, slots 3 and 4, and slots 5 and 6 are valid pairs. Slots 2 and 3 are not a valid pair.

Terminal block connections

Table: Redundant Discrete Input 40-Pin Mass Termination Block cable pin outs

J5 connector

Signal

J6 connector

Signal

Pin 1 Channel 1 Pin 1 Channel 17
Pin 2 Channel 2 Pin 2 Channel 18
Pin 3 Channel 3 Pin 3 Channel 19
Pin 4 Channel 4 Pin 4 Channel 20
Pin 5 Channel 5 Pin 5 Channel 21
Pin 6 Channel 6 Pin 6 Channel 22
Pin 7 Channel 7 Pin 7 Channel 23
Pin 8 Channel 8 Pin 8 Channel 24
Pin 9 Channel 9 Pin 9 Channel 25
Pin 10 Channel 10 Pin 10 Channel 26
Pin 11 Channel 11 Pin 11 Channel 27
Pin 12 Channel 12 Pin 12 Channel 28
Pin 13 Channel 13 Pin 13 Channel 29
Pin 14 Channel 14 Pin 14 Channel 30
Pin 15 Channel 15 Pin 15 Channel 31
Pin 16 Channel 16 Pin 16 Channel 32
Pin 17 Left cable detection Pin 17 Right cable detection
Pin 18 +24 V Pin 18 +24 V
Pin 19 Left cable detection Pin 19 Right cable detection
Pin 20 +24 V Pin 20 +24 V