| Channel type and functionality
|
Analog input:
- 4-20 mA
- 0-20 mA
- 4-20 mA with HART
|
| Nominal signal range (span)
|
|
| Full signal range
|
0-24 mA
|
| Input impedance
|
250 Ω ±1%
|
| 2-wire transmitter power
|
15.0 V minimum at 20 mA with 24 VDC input
power.
|
| Accuracy over temperature range
|
- 0.1% of span (0 to
60° C)
- 0.25% of span
(-40-70° C)
|
| Repeatability
|
0.05% of span
|
| Resolution
|
16-bit
|
| Calibration
|
None required
|
| Input power requirements
|
Total power requirement: +24 VDC ±10% at 32
mA maximum for 2-wire configurations and 8 mA maximum for 4-wire
configurations:
- Input power from
CSLS Power Modules: +6.3 VDC ±3% at 20 mA maximum
- +24 VDC input
power: +24 VDC ±10% at 25 mA maximum
|
| CHARM heat dissipation
|
0.33 W
|
| HART scan time
|
Typically less than one second but is
dependent on HART communication loading and the capability of the HART device.
|
| HART Communications
|
- HART pass-through
request/response
- HART variable
report
- Field device
status report
|