Equipment definition > Equipment module classes > Configuring the TOTALIZER equipment module class

Configure the logic for COMMAND_00002 (Totalize_accurate)

  1. Click COMMAND_00002 in the left pane.
  2. Click the S1 step.
  3. Add an action and configure the following expression:
    '^/TOTAL_FLOW_1/RESET.CV' := FALSE
  4. Add another action andconfigure the following expression:
    '^/FLOW_CONTRO_1/PID_MODE.TARGET' := CAS
  5. Add another action and create the following expression:
    '^/FLOW_CONTRO_1/PID_CAS_IN.CV' := 0.25 * '^/FLOW_CONTRO_1/PID_SP_HI_LIM.CV'

The Reset logic is used to reset the integrator block in the TOTAL_FLOW control module and to put FLOW_CONTROL into manual mode.