User-defined export, import, and bulk editing > Bulk editing configuration objects > Bulk editing equipment and control modules

Equipment and control module syntax table

To successfully export and import a module(1) it must be based on a template. 

Note

If a module is not created from a module template, you must create a template for the module to successfully export and import it with a user-defined format. 

Table: Valid Field Values for Equipment and Control Modules

Field

Valid Values

Required for Import

description

As many as 255 characters using any keyboard characters.  Note that only the first 24 characters appear in faceplates.

No

node_name

Any valid node name

No

area

Any valid area name. If the area does not exist or is not specified, the module is imported into AREA_A.

No(1)

module_name

Module name. As many as 16 characters. The string must contain one letter and can include the following: $, -, _.

Yes

work_in_progress

T or F

No

restore_param_vals

T or F

No

param_download_behavior

Select from list

No

module_type 

A string containing any keyboard characters

No

module_subtype

An existing module subtype(2)

Yes(2)

scan_rate

0.1 = 100 ms

0.2 = 200 ms

0.5 = 500 ms

1 = 1 second

2 = 2 seconds

5 = 5 seconds

10 = 10 seconds

30 = 30 seconds

60 = 60 seconds

No

primary_display

Any valid picture name

No

detail_display

Any valid picture name

No

faceplate_display

Any valid picture name

No

equip_arbitration

T or F

No(3)

equip_id

Unique ID between 1 and 65535

No(3)

max owners

Number of simultaneous users

No(3)

Parameter List

Depends on subtype

No

Alarms(4)(5)

ALARM_TYPE

Any valid alarm type.

No

PRI

Alarm priority

No

ENAB

Alarm enabled? T or F.

No

INV

Alarm inverted? T or F.

No

ALARM_ATTR

The parameter that the alarm monitors.

No

MSG_PARAM1

Alarm message parameter 1

No

MSG_PARAM2

Alarm message parameter 2

No

SUPPRESS_TIMEOUT

Alarm shelving timeout

No

ALARM_DESCRIPTION

User-configured alarm description. As many as 255 characters (approximately the first 36 characters are visible in the DeltaV alarm banner).

No

(1) The system looks up the correct area on import. If the area cannot be found, the module is imported to AREA_A.
(2) This field is required. If you do not provide this field, the system imports an empty module with default parameters. The name in this field must match the name of the module template that the structure of the new module is based on.
(3) Applies only to modules used in batch systems.
(4) Each module alarm has the following fields. In the bulk edit file each field is prepended with the alarm name. For example, ALARM1.ALARM_TYPE.
(5) The alarm fields also include DeltaV Alarm Help fields that are discussed elsewhere.
(1) Phase logic modules are not supported.