User-defined export, import, and bulk editing > Bulk editing configuration objects > Bulk editing Ethernet I/O Cards (EIOC)

OPC UA signal syntax table

Table: Valid field values for OPC UA signals

Field

Valid values(1)

Required for import

controller_node_name

The name of the EIOC or workstation containing the signal

Yes

physical_device_node_name

The name of the ancestor physical device

Yes

logical_device_node_name

The name of the parent logical device

Yes

signal_name

The name of the signal

Yes

protocol

OPC UA

Yes

description

As many as 255 characters using any keyboard characters

No

signal_tag

The device signal tag

No

data_direction

Input or Output

No

data_type

  • FLOAT_WITH_STATUS
  • UNICODE_STRING_WITH_STATUS
  • UINT32_WITH_STATUS
  • UINT16_WITH_STATUS
  • UINT8_WITH_STATUS
  • INT32_WITH_STATUS
  • INT16_WITH_STATUS
  • INT8_WITH_STATUS
  • BOOLEAN_WITH_STATUS

No

node_id

The node ID string

No

value_rank

  • ARRAY
  • SCALAR

No

array_index

An array index number, expressed as n[,n...,n]

No

(1) All field values are treated as a string