This section outlines how to bulk edit EIOC nodes, ports, physical and
logical devices, and signals. The general procedure to bulk edit EIOC objects
is:
Create an EIOC card.
Configure the card's ports.
Under the port create and configure a physical device of the type
you want to bulk edit.
Under the physical device create and configure a logical device of
the type you want to bulk edit.
Under the logical device configure the signals.
For each level (EIOC, logical device, physical device, signal) use
the sample format specification files or create your own and export data from
the existing configuration.
Note
The EIOC port is bulk edited with the EIOC.
In DeltaV Explorer, select the EIOC object that you want to export
and select
File → Export → User
Defined to create a text file for import.
Edit the text file for the EIOC object in the bulk edit Excel
add-in.
Import the text file for the EIOC object into the DeltaV Explorer.