User-defined export, import, and bulk editing > Bulk editing configuration objects > Bulk editing CHARM I/O cards and CHARMs

CIOC syntax table

DeltaV includes the cioc.fmt file for bulk editing only CHARM I/O cards. Or you can create your own format file. The fields available when you create a format file are listed in the following table. 

Field Names

Valid Values

Required for Import

cioc_name

16 characters or fewer. The string must contain at least one alphabetical character and can include letters, numbers and the following characters: $, -, and _.

Yes

description

255 characters, alpha-numeric

No

alarm_area

Area that alarms and events are associated with. 

No

system_hardware_alarms

T, F

No

enable_network_redundancy

T, F

No

enable_cascade_port

T, F

No

show_integrity_error

T, F

No

node_is_redundant

T, F

No

simulate_charms

T, F

No

cioc_scan_rate

50, 100, 250, or 500 ms

No