DeltaV includes the cioc.fmt file for bulk editing only CHARM I/O cards. Or you can create your own format file. The fields available when you create a format file are listed in the following table.
Field Names |
Valid Values |
Required for Import |
|---|---|---|
cioc_name |
16 characters or fewer. The string must contain at least one alphabetical character and can include letters, numbers and the following characters: $, -, and _. |
Yes |
description |
255 characters, alpha-numeric |
No |
alarm_area |
Area that alarms and events are associated with. |
No |
system_hardware_alarms |
T, F |
No |
enable_network_redundancy |
T, F |
No |
enable_cascade_port |
T, F |
No |
show_integrity_error |
T, F |
No |
node_is_redundant |
T, F |
No |
simulate_charms |
T, F |
No |
cioc_scan_rate |
50, 100, 250, or 500 ms |
No |