Refer to the following table when creating format specification files and bulk editing history data points.
Field |
Valid Values |
Required for Import |
|---|---|---|
value_recorded |
Path to the parameter and field being recorded |
Yes |
enable |
T = collect parameter data F = do not collect parameter data |
No |
display_representation |
STEP: Changes are shown as step changes. LINE: Values are connected by lines. AUTOMATIC: The software determines the representation based on data type. |
No |
data_characteristic |
CONTINUOUS: Data is coming from the process. MANUAL: Operator is entering values. |
No |
sampling_period |
1, 2, 5, 10, 30, 60, or 300 seconds |
No |
compression_enabled |
T = enabled F = disabled |
No |
deviation |
Sets the amount of change which results in a sample being stored. |
No |
at_least |
15, 60, 240, 480, 1080, 1440 minutes. |
No |
hdp_type |
Definition(1) Configurable(2) Override(2) Instance(3) |
No |
use_default |
T = Use default value from module class check box in module instance is checked. F = Use default value from module class check box in module instance is not checked. <NULL> = The hdp_type is Definition or Instance. |
No |
en_col_enabled |
T = Enterprise data collection enabled. F = Enterprise data collection disabled. |
No |