LSNG Secure Parameters are mapped into publishers when their corresponding Signal is created in the LSNG configuration. Referencing them does not affect their mapping. Each LSNG supports as many as 4 publishers.
Secure data from the LSNG appears to the LSNB just like data from a CSLS and can be mapped to be sent to other LSNs. In addition, commands to the Modbus devices can come from CSLSs on other LSNs through the LSNB.
| Local Safety Network Gateway property | Limit |
|---|---|
|
LSNGs per local safety network |
4 (3 if the LSN contains an LSNB) |
|
Publishers per LSNG |
4 |
|
Publishers per LSN |
8 |
|
Boolean Secure parameters per publisher |
192 |
|
Boolean Secure parameters per LSNG |
768 |
|
Modbus devices per LSNG |
2 |