Limits (AI_DT)

  • Hi Hi Lim - This field displays the maximum value of the PV in engineering units before the high high limit active bit (HI_HI_ACT) is set. Click this field to enter a new limit.

  • Hi Lim - This field displays the maximum value of the PV in engineering units before the high limit active bit (HI_ACT) is set. Click this value to enter a new limit.

  • Lo Lim - This field displays the minimum value of the PV in engineering units before the low limit active bit (LO_ACT) is set. Click this value to enter a new limit.

  • Lo Lo Lim - This field displays the minimum value of the PV in engineering units before the low low limit active bit (LO_LO_ACT) is set. Click this field to enter a new limit.

  • Alm Hysteresis - This field displays the alarm hysteresis (or deadband) value for the AI alarms in percent of Out scale. Click this value to enter a new value. An alarm does not recur until the PV has backed away from the corresponding limit by at least the percent of Out Scale specified by this value.

  • Low Cutoff (LOW_CUT) - Activated when the Low Cutoff I/O option is enabled. When the converted measurement is below the LOW_CUT value, it is shown in the PV as 0.0.