The frsVariables listed here affect how dynamos (from sets named *_Theme) show different status information as well as set the visibility on the dynamo components. These variables are not changed during runtime. For example, if you do not want to have the status box indication when a pump has a permissive active (but has not caused an interlock), you can set the variable: ShowBorderDCWrongMode to FALSE.
Change these global variables in the User_Ref picture by un-commenting the variable and changing the setting to override the system defaults. Refer to Customizing the DeltaV Operate Environment.
|
Variable |
Description |
|---|---|
|
gb_almPriChgButtonVisible |
Determines the visibility of the Change Alarm Priority button in a standard DeltaV Operate display. |
|
gb_mnoFalseAtRunTime |
Disables at runtime the visibility of the Multipoint dynamo rectangle visible during configuration |
|
ShowBorderBadIO |
Determines the visibility of the status border when the Bad I/O is present in the module (default=Show) |
|
ShowBorderDCWrongMode |
Determines the visibility of the DC module dynamos’ status border when the actual mode of the DC block is not the same as the normal mode or not the same as the target mode (default=Show) Note: Permissive Not Present condition causes LO mode |
|
ShowBorderNotRunning |
Determines the visibility of the status border when the module is not running (default=Show) |
|
ShowBorderSim |
Determines the visibility of the status border when Simulate is Active (default=Show) |
|
ShowBorderWrongMode |
Determines the visibility of the analog module dynamos’ status border when the actual mode is not the same as the normal mode or not the same as the target mode (default=Show) |
|
ShowComboBar |
Shows/hides the combo or deviation bar graph on horizontal dynamos (default=Show) |
|
ShowScale |
Shows/hides the scale marks on the out bar graph (default=Show) |
|
ShowTag |
Shows the module name, description, friendly name, or nothing based on user selection from a toolbar button |