Module dynamos, faceplates, and detail displays > Module template dynamos > FrsModules dynamo reference

MPCPro input variable dynamo (MV/DV)

The MPCPro Input Variable Dynamo can be used for both Manipulated and Disturbance variables.

If you use the browse button to configure an MPCPro Input variable dynamo you must edit the Node.Module/FB_Name field on the Dynamo Properties dialog and remove the parameter and field names that are added as a result of the browse. This field must contain only node, module, and function block name. Parameter and field names are not allowed. For example if the field is populated with Node1.MyModule/MPC-Pro1/Proc_IN.F_CV after the browse, edit it to Node1.MyModule/MPC-Pro1.

You must include the actual input variable name (MV or DV) in the Parameter Description field on the Dynamo Properties dialog.