Place a fieldbus device in the standby state

Devices in the offline, mismatch, or spare state must be placed in the standby state before they can be commissioned.

  1. Navigate to the fieldbus device (System Configuration/Physical Network/Control Network/controller/I/O/card/port/Decommissioned Fieldbus Devices).
  2. Right-click the device in the right pane.
    Note:
    A device in the offline or spare state will have the state name listed in its detailed view in the right pane. If the detailed view is not showing, click View → Details. If you want to commission a mismatch device, place it in offline or spare, then place it in standby, then commission it.
  3. Click Standby.
    Note:
    The Do Not Wait notice appears. If you click this, the state change continues in the background, but the notice goes away, enabling you to do other work.

When the device changes to a Standby Device, it is ready for commissioning.