The minimum valid temperature for saturated steam is the higher of 383°F (195°C) or the saturation temperature for the input pressure.
The block calculations are based on The International Association for the Properties of Water and Steam (IAPWS) Revised Release on the IAPWS Industrial Formulation 1997 for the Thermodynamic Properties of Water and Steam.
If the input values are out of the specified IF97 range, the values used for calculation are limited to the IF97 boundary values and the block status is set to Bad.
The following figure shows the internal components of the STM function block.
STM function block schematic diagram