Steam Properties function block application
information
The STM function block calculates steam enthalpy, entropy, and specific
volume for a given gauge pressure and a given temperature. The block
calculations apply to superheated steam and saturated steam.The valid ranges
are:
Temperature: 32 to 3632°F (0
to 2000°C)
Pressure:
P > -14.696 psig (0
Mpa )
P <= 14489 psig (100 Mpa)
for temperature < 1472°F (800°C)
or
P <= 7237.1 psig (50 Mpa )
for temperature => 1472°F (800°C)
The minimum valid temperature for saturated steam is the higher of 383°F
( 195°C) or the saturation temperature for the input pressure.