The following table lists the system parameters for the Deadtime function block:
|
Parameter |
Units |
Description |
|---|---|---|
|
ABNORM_ACTIVE |
None |
The indication that a block error condition not selected in BAD_MASK (on the function block level) is True (Active) or the indication that an error condition (at the module level) not selected in MERROR_MASK is True (Active) or a module status not selected in MSTATUS_MASK is True (Active). |
|
BAD_ACTIVE |
None |
The indication that a block error condition selected in BAD_MASK (at the function block level) is True (Active) or the indication that an error condition (at the module level) selected in MERROR_MASK is True (Active) or a module status selected in MSTATUS_MASK is True (Active). |
|
BAD_MASK |
None |
The set of active error conditions that triggers a user-defined Bad condition. The user selects a subset of block error (BLOCK_ERR) conditions in the BAD_MASK parameter. When any of these conditions are True, the BAD_ACTIVE parameter becomes True. When any of the BLOCK_ERR conditions that are not included in BAD_MASK are True, ABNORM_ACTIVE becomes True. |
|
BAL_TIME |
Seconds |
Specifies the time for the internal value of the delay input signal to match the OUT value. |
|
BLOCK_ERR |
None |
The summary of active error conditions associated with the block. The possible block error for the Deadtime function block is:
|
|
DEAD_TIME |
Seconds |
Time delay introduced in the input signal to generate the output value. Enter a value between 0 and 32400. |
|
FOLLOW |
None |
Allows OUT to track IN (True [1] = active, False [0] = inactive). |
|
IN |
Determined by source |
The input value and status to be delayed by the block. |
|
MODE |
None |
Parameter used to request and show the source of the output used by the block. |
|
OUT |
EU of IN |
The primary value and status calculated by the block in Auto mode. OUT can be set manually in Man mode. |
Default values and data type information for the parameters are available by expanding the Parameter View window.