| CommStatus
|
Port A Not Present
|
Indicates the PortA IOP cannot be communicated
with, normally this means the IOP has been unplugged.
|
| Port B Not Present
|
Indicates the PortB IOP cannot be communicated
with, normally this means the IOP has been unplugged.
|
| Port A no Comms
|
Indicates the PortA IOP is present but is not
receiving valid distributed CHARMs messages.
|
| Port B no Comms
|
Indicates the PortB IOP is present but is not
receiving valid distributed CHARMs messages.
|
| Port A Wrong IOP type
|
Indicates the PortA IOP type, Star/Ring does
not match the type that the scanner module detected at startup. This would
happen if the Single Port Ring IOP was replaced by an 8 Port Star IOP or vice
versa. This only applies to the Gateway.
|
| Port B Wrong IOP Type
|
Indicates the PortB IOP type, Star/Ring does
not match the type that the scanner module detected at startup. This would
happen if the Single Port Ring IOP was replaced by an 8 Port Star IOP or vice
versa. This only applies to the Gateway.
|
| Ring Broken
|
When the Gateway and Blocks are in a ring
configuration this indicates that there is a break somewhere in the ring, all
scanner modules in the ring will show this error.
|
| DeviceStatus
|
Primary 24 Volt Power Invalid
|
Indicates the Primary 24 Volt power is below
the allowed value.
|
| Secondary 24 Volt Power Invalid
|
Indicates the Secondary 24 Volt power is below
the allowed value.
|
| Firmware Upgrade Pending
|
Indicates that the scanner module has received
a new firmware image and is waiting for the user to initiate the upgrade. This
should only be seen on simplex scanner modules as a redundant would go ahead
and upgrade.
|
| Firmware Upgrade In Progress
|
Indicates that a firmware upgrade is in
progress.
|
| Firmware Mismatch
|
Indicates that the Block has a different
version from the Gateway and will upgrade before it goes online. Only applies
to blocks.
|
| 6 Volt Power Invalid
|
Indicates the 6.3 Volt power is below the
allowed value.
|
| 24 Volt Over Current
|
Indicates the current on the 24V power has
exceeded the allowed value.
|
| Address Plug Error
|
Indicates that the Address Plug is either not
present or has a different value from that read at startup. Only applies to
blocks.
|
| IOStatus
|
Primary Charm Bus Problem
|
Indicates that the scanner module is having a
problem on the Primary CHARM bus.
|
| Secondary Charm Bus Problem
|
Indicates that the scanner module is having a
problem on the Secondary CHARM bus.
|
| Primary Bus Tx Error
|
Indicates that the scanner module has a
Primary Slicebus transmitter issue.
|
| Primary Bus Rx Error
|
Indicates that the scanner module has a
Primary Slicebus transmitter issue.
|
| Secondary Bus Tx Error
|
Indicates that the scanner module has a
Secondary Slicebus transmitter issue.
|
| Secondary Bus Rx Error
|
Indicates that the scanner module has a
Secondary Slicebus transmitter issue.
|
| Charm Error
|
Indicates that there is at least one charm
that has bad integrity. Only applies to blocks.
|
| RedundStatus
|
Partner Not Available
|
Indicates that the standby scanner module in a
redundant setup is not currently available to take over.
|
| Partner Not Present
|
Indicates that the standby scanner module in a
redundant setup is not physically present.
|
| Dual Active Scanner Modules
|
Indicates that both the scanner modules in a
redundant setup think they should be the active. This normally indicates a
redundancy link failure, only one scanner module will actually go active as
only one can communicate on the slicebus and distributed CHARMs network.
|