The Rosemount Statistical Process Monitoring (SPM) Library Module Templates (RMT_SPM_HART and RMT_SPM_FF) provide a means to easily configure alarms, process history collection, and operator faceplates for Rosemount field devices that implement Statistical Process Monitoring (SPM) technology. The RMT_SPM_HART template is used for HART devices that implement SPM Technology (for example, Rosemount 3051S with Advanced HART Diagnostics), while the RMT_SPM_FF template is used for Foundation Fieldbus devices that implement SPM (for example, Rosemount 3051S FF with Advanced Diagnostics Suite). SPM data (PV, Mean, Standard Deviation, and Coefficient of Variation) generated by the field device are brought into Control Studio via AI Function Blocks. The Module Templates provide pre-configured, history collection, alarms, and alarm management.