Refer to the following table when creating format specification files for and bulk editing SIS modules.
|
Field |
Valid Values |
Required for Import |
|---|---|---|
|
description |
As many as 255 characters using any keyboard characters. Note that only the first 24 characters appear in faceplates. |
No |
|
logic_solver |
The Logic Solver this module is assigned to. If the Logic Solver does not exist, the module is imported but not assigned. |
No |
|
area |
Any valid area name. If the area does not exist or is not specified, the module is imported into AREA_A. |
No |
|
module_name |
As many as 16 characters. The string must contain one letter and can include the following: $, -, _. |
Yes |
|
work_in_progress |
T or F |
No |
|
module_type |
A string containing any keyboard characters |
No |
|
module_subtype(1) |
An existing module subtype |
Yes |
|
primary_display |
Any valid picture name |
No |
|
detail_display |
Any valid picture name |
No |
|
faceplate_display |
Any valid picture name |
No |
|
risk_red_factor |
Risk reduction factor |
No |
|
Parameter List |
Depends on subtype |
No |
|
ALARM_TYPE |
Any valid alarm type. |
No |
|
PRI |
Alarm priority |
No |
|
ENAB |
Alarm enabled? T or F. |
No |
|
INV |
Alarm inverted? T or F. |
No |
|
ALARM_ATTR |
The parameter that the alarm monitors. |
No |
|
MSG_PARAM1 |
Alarm message parameter 1 |
No |
|
MSG_PARAM2 |
Alarm message parameter 2 |
No |
|
SUPPRESS_TIMEOUT |
Alarm shelving timeout |
No |
|
ALARM_DESCRIPTION |
User-configured alarm description. As many as 255 characters (approximately the first 36 characters are visible in the DeltaV alarm banner). |
No |