The Fused 8-channel
terminal block is recommended to provide terminations for field wiring for the
DO 8-channel 24 VDC high-side card. Optional terminal blocks are the 8-channel
terminal block and the 16-pin mass terminal block. If you use a mass terminal
block with the DO 8-channel 24 VDC high-side I/O card, refer to the terminal
block specifications for the output rating for each block. Those specifications
might be more restrictive than the specifications listed in the following
table.
The Redundant Discrete
8-channel terminal block is recommended to provide terminations for field
wiring for the redundant DO 8-channel 24 VDC high-side card.
The DO 8-channel 24 VDC
high-side card has line fault detection that can be enabled on a
channel-by-channel basis as a configuration item. When line fault detection is
enabled, the card detects open and short line fault conditions by performing an
internal readback of the output to verify its value in both on and off states.
The card tests the opposite state of its current value by temporarily changing
the output to that value, performing the internal readback, then returning the
output to its configured output value. The pulses to the opposite state are
never greater than 200 microseconds. High speed inputs that connect to a DO
channel with line fault enabled must consider these pulses in the input
software scheme. When line fault detection is not enabled, a more limited
detection of open and short line fault conditions is available on the active
redundant card only. This is accomplished by the internal readback mechanism
without pulsing the output to the opposite state. Therefore, shorts can be
detected only when the DO channel is on, and opens can be detected only when
the DO channel is off. When line fault detection is not enabled, and the card
is simplex, line fault tests do not run and line fault conditions are not
reported.
When pulse testing is
enabled, the LED on the output device may be slightly illuminated.
This card requires an
S-series controller.
Note
Line fault detection is not compatible with significant capacitive
loading (cable + load > 30 nF) and must be disabled under these conditions.
Table: Line fault detection levels
Line fault detection
Value detected
Short circuit
<5 Ω for >3 seconds
Open circuit
>25 kΩ for
guaranteed open loop detection
< 8 kΩ for
guaranteed no open loop detection
Specifications
Table: DO 8-channel 24 VDC high-side card specifications
Item
Specification
Number of channels
Eight
Output range
24 VDC ±10%
Output rating
1.0 A continuous
per channel (inrush 4.0 A for <100 ms; 6.0 A for <20 ms)
3.0 A maximum per
card
Off-state leakage
1.2 mA maximum
Configurable channel types
Discrete output
If FAIL_ACTION_MODE is Hold last value
(default): Output stays in last state submitted by the controller.
If FAIL_ACTION_MODE is Go to configured
failure action mode: Output is driven to the configured faultstate value.
Momentary output
If FAIL_ACTION_MODE is Hold last value
(default): Output finishes current pulse.
If FAIL_ACTION_MODE is Go to configured
failure action mode: Output is driven to the configured faultstate value and
the channel is re-configured as a latched output.
Continuous pulse output
If FAIL_ACTION_MODE is Hold last value
(default): Output continues pulsing.
If FAIL_ACTION_MODE is Go to configured
failure action mode: Output is driven to the configured faultstate value and
the channel is re-configured as a latched output.
LocalBus current (12 VDC nominal), per card
Simplex:
100 mA typical
150 mA maximum
Redundant:
90 mA typical
150 mA maximum
Field circuit power, per card
3.0 A at 24 VDC (±10%)
Isolation
Each channel is optically isolated from the
system and factory tested to 1500 VDC.
Heat dissipation
3.9 W for simplex and redundant
Optional fuse (Simplex mode only)
2.0 A (inrush 5.0 A for <10 ms at 0.1%
duty cycle)
Mounting
Assigned slot of I/O carrier
Wiring diagrams
Figure: Simplex DO 8-channel 24 VDC high-side card wiring
diagram
Figure: Redundant DO 8-channel 24 VDC high-side card wiring
diagram