DeltaV Vertical Carriers > Installing VerticalPLUS Carriers > Extending LocalBus Power to Other Carriers

Extend power from left to right 8-wide VerticalPLUS carriers

Be sure that the DIN rail stops are in place on both DIN rails. Refer to “Installing the DIN Rail Stop”.

This procedure is for an installation with 6 carriers.

  1. Connect a left 1-wide VerticalPLUS carrier extender to the last 8-wide carrier on the left side (carrier 3) by sliding together the 96 pin connectors on the carriers.
  2. Connect a right 1-wide VerticalPLUS carrier extender to the first 8-wide carrier on the right side (carrier 4) by sliding together the 96 pin connectors on the carriers.
  3. Connect the 25 pin D-shell (male) connector on the extender cable to the D-shell connector labeled A on the left 1-wide carrier extender and fasten the retainer screws.
  4. Connect the 25 pin D-shell connector on the other end of the cable to the D-shell connector labeled A on the right 1-wide carrier extender and fasten the retainer screws.