To specify the location and type of LS CHARMs associated with the field measurement, you configure the LS CHARM and the Device Signal Tag (DST) of the input or output parameter. The following LS CHARM classes are available in CSLSs.
| CHARM Class | Description | Type | Functionality | Function Block Use |
|---|---|---|---|---|
| Analog Input | Reports the analog value present and up to four digital values from a HART field device. |
LS AI 4-20 mA HART LS AI 4-20 mA HART (Intrinsically Safe) LS AI Generic |
HART Analog Input 4-20 mA Analog Input 4-20 mA Analog Input 0-20 mA |
Used with LSAI function blocks as input I/O references. Used with LSAI function blocks as readback references to read a 4 to 20 mA signal. |
| Discrete Input | Reports the discrete value present at the channel |
LS DI NAMUR LS DI 24 VDC Low-Side LS DI 24 VDC Isolated LS DI 120 VAC Isolated LS DI 120 VAC Isolated Plus LS DI 230 VAC Isolated LS DI NAMUR (Intrinsically Safe) LS DI Generic |
Discrete Input |
Used with LSDI function blocks as input I/O references when reading a discrete (On/Off) signal. Used with LSDO function blocks as a readback I/O reference for a discrete signal. |
| Thermocouple_mV | Reports the temperature of the thermocouple and is cold junction compensated |
LS Thermocouple/mV LS Thermocouple/mV (Intrinsically Safe) LS Thermocouple/mV Generic |
Type B Thermocouple Input Type E Thermocouple Input Type J Thermocouple Input Type K Thermocouple Input Type N Thermocouple Input Type R Thermocouple Input Type S Thermocouple Input Type T Thermocouple Input ±20 Millivolt Input ±50 Millivolt Input ±100 Millivolt Input |
Used with LSAI function blocks as input I/O references. |
| RTD | Reports the temperature or ohms of the RTD bulb. |
LS RTD / Resistance Input LS RTD / Resistance Input (Intrinsically Safe) LS RTD Generic |
Pt 100 RTD Input Pt 200 RTD Input Pt 500 RTD Input Pt 1000 RTD Input Ni 120 RTD Input Ni 100 RTD Input Ni 200 RTD Input Ni 500 RTD Input Ni 1000 RTD Input Cu 10 RTD Input Resistance RTD Input |
Used with LSAI function blocks as input I/O references |
| Voltage | Reports the analog value present |
LS AI 0-10 VDC Isolated LS Voltage Generic |
0 to 5 Volt Input 0 to 10 Volt Input 1 to 5 Volt Input -1 to +1 Volt Input -5 to +5 Volt Input -10 to +10 Volt Input |
Used with LSAI function blocks as input I/O references |
| Power |
LS 24 VDC Power LS Power Generic |
24 VDC Power | Used with LSDI function blocks as input I/O references when reading a discrete (On/Off) signal |
| CHARM Class | Description | Type | Functionality | Function Block Use |
|---|---|---|---|---|
|
Discrete Output |
Drives the output to a discrete value and holds the output at that value. Outputs immediately reflect the output value that was received. |
LS DO 24 VDC DTA LS DO 24 VDC ETA LS DO Generic |
Discrete Output |
Used with LSDO function blocks as output I/O references when driving as discrete signal |
|
Redundant Discrete Output |
LS DO 24 VDC (Redundant DTA) LS DO 24 VDC (Redundant ETA) LS DO Redundant Generic |
|||
|
Two-State DVC Output |
Drives a digital valve controller output device with an On value of 20 mA. The Off value is configurable: either 0 mA or 4 mA (to allow for HART communications). |
LS DVC HART DTA LS DVC HART Generic |
0/4mA & 20mA with HART Output |
Used with LSDVC blocks to drive DVC6000ESD digital valve controllers. |
|
Redundant Two-State Output |
LS DVC HART (Redundant DTA) LS DVC HART Redundant Generic |