Logical Blocks > Discrete Control Condition (DCC) function block

Discrete Control Condition function block configuration and execution

The following sections cover aspects of DCC block configuration and their effect on block execution.

The DCC block supports up to 16 interlock conditions, 8 permissive conditions, and 8 force setpoints. For each condition configure the following:

The three condition types have several similar parameters describing different properties of each condition. When discussing these similar parameters in general the following convention is used: a_PARAMn. For example a_OUT_Dn. OUT_D is the parameter root, a represents the three types of conditions (I, P, and F), and n represents the condition number. For example, a_OUT_Dn represents instances of I_OUT_D_[1-16], F_OUT_D_[1-8], and P_OUT_D_[1-8].

Note

References to the I_OUT_D_n, P_OUT_D_n and F_OUT_D_n function block parameters are not updated when the Move Up and Move Down buttons are used to change the order of the conditions.