Power in a DeltaV system

The DeltaV system uses system power supplies and bulk power supplies to power the controllers, CIOCs, and I/O subsystems.

Power in an S-series system

In a DeltaV system with S-series hardware, power is distributed from bulk power supplies to system power supplies and then to controllers and the I/O subsystems along the LocalBus. The LocalBus is the internal power and communications bus running through the connected S-series carriers. The LocalBus supports up to 15 A. System power is shared along the length of the LocalBus.

Field power for S-series I/O can be individually delivered to each card or separately delivered to primary and redundant cards through connectors on the S-series 8-Wide I/O Carrier. Refer to the DeltaV S-series and CHARMs Hardware Installation manual for step-by-step instructions on how to deliver field power to individual cards and to redundant cards. Refer also to the specifications for the 8-Wide I/O Carrier in this manual for an image showing the field power connectors on the carrier.

Power in a CHARMs I/O system

The CHARM I/O Carrier accepts redundant 24 VDC from primary and secondary bulk power supplies connected to two 24 VDC input terminals on the carrier. This power is used by redundant CHARM I/O Cards (CIOCs) and is available to each CHARM to power field devices. In addition, the CIOC powers a redundant 6.3 VDC bus that provides internal power for each CHARM.

Types of power supplies used

The DeltaV system uses system power supplies and bulk power supplies. System power supplies power DeltaV controllers and I/O subsystems. Bulk power supplies power system power supplies, CIOCs, and field devices.